The ASD-NANOCOM multiprotocol communication interface provides RS-485-based network connectivity to Toshiba Q7/G7/H7/W7-series adjustable speed drives (ASDs). The ASD-NANOCOM connects directly to the drive's control board, and uses the drive's RS-485 port for network communications.
The ASD-NANOCOM supports four user-selectable registers can be designated for special processing. The use of these registers is protocol-dependent. An optional 1s-255s network timeout time can be selected. If a timeout setting is selected, then after the designated period of network inactivity the interface will perform actions to place the drive in a "failsafe" state. The specific action taken is protocol-dependent.
The Modbus RTU protocol allows all ASD parameters numbered FA00 - FFFF to be accessible as Modbus holding registers both at 0xFA00 - 0xFFFF (64000 - 65535) as well as 0x0A00 - 0x0FFF (2560 - 4095). This allows master devices that can index only 9999 total holding registers to access all available ASD information.
Manuals Version Information Firmware- All ASD-NANOCOM units with serial number 10544043 or higher have been released with firmware version 2.100.
- All ASD-NANOCOM units with serial number 10543742 or higher have been released with firmware version 2.000.
- All others were released with firmware V1.000.
Associated Links
Additional Information
| Network Interface | RS-485 |
|---|---|
| Protocols | Siemens FLN Slave, Metasys N2 Slave, Modbus RTU Slave |
| Power Supply | ASD |
| User Configuration Interface | N/A |
| Alarms | No |
| Network Timeout Action | Yes |
| Mounting Options | Internal |
| Mounting Hardware Included | Yes |
| Configuration File Upload/Download | No |
| Field-Upgradeable | No |
| LED Indicators | No |
| ROHS Compliant | Yes |